Case Study: What is 3 Minutes of Motor Testing Worth to You?

The Company:

A motor distributor in the Netherlands provided a 17 Kilowatt, 400-Volt motor to a local hospital in 2015. The hospital rented a portable crane to install the motor onto the roof of the building. The motor is used to operate a fan that is mounted on the hospital’s roof. In the spring of 2016, the motor suddenly stopped running, so the motor distributor was contacted for field service, troubleshooting, and on-site support.

 

The Challenge:

The motor had been connected to a Variable Frequency Drive (VFD), and when the motor stopped running, the hospital’s maintenance technician reset the VFD. The motor did start, but unfortunately, the VFD shut the motor down again. Next the technician performed an insulation-to-ground test and determined the motor winding was not shorted to ground. Using a DMM (Digital MultiMeter) he then measured phase resistance and learned the phases were not open. The motor testing tools the technician used pointed to a “good” motor; therefore, they decided to replace the VFD. After the new VFD had been installed, the motor started up, but did not continue to run. Much to the technicians’ chagrin, they were experiencing the same problem; which compelled the hospital’s maintenance manager to contact the distributor who had supplied the hospital with the motor. The responsive motor distributor, who has a service center and support staff, sent one of their technicians to the hospital to test the motor. The service center technician used a meg-ohm meter and Digital Multi-meter (DMM) to determine that the motor was not grounded and the phases were not open; which was no different from the previous test results. Since the motor still did not run, the decision was made to replace the motor. A crane was brought in to remove the motor from the roof of the hospital and allow a replacement motor to be installed. The replacement motor started and operated normally, confirming the new VFD was working as intended. The “suspect” motor was sent to the service center for a more thorough inspection.

 

The Solution: 

3 Minutes of Motor Testing at the Service Center An ALL-TEST PRO 5™ (pictured to the right) was used to perform a de-energized, non-destructive Motor Circuit Analysis (MCA) test at the service providers’ facility. Motor Circuit Analysis evaluates the condition of the electric motor connections, stator, and rotor in just minutes. Using the AT5™, connections were made to the three phases of the motor and a static test was performed. Next, the motor shaft was manually moved during the dynamic portion of the 3-phase test, and at the end of the test the instrument showed the results (as shown on the right). When performing the dynamic test between phases 2-1, it became clear that this was the phase that had the problem.

 

Lessons Learned:

Owners / Operators Can Reduce Maintenance Costs A 17kW, 400V motor is not expensive, but when it is mounted on the roof of a building, and the owner has to rent a crane to lift that motor for installation and removal, the cost to the owner can become extremely expensive when it comes to maintenance and reliability. If the hospital’s maintenance team had owned and utilized a Motor Circuit Analysis instrument such as the ALL-TEST PRO 5™ or ALL-TEST PRO 33IND™, then they would have been able to tell right away that the motor had been the “bad actor” and not the VFD. Many hours were wasted by ordering and installing a new VFD when it had not been the true cause of the problem.

 

Distributors and Suppliers Can Improve Quality Assurance:

Motor distributors and suppliers should implement an additional quality control measure prior to delivering new or off-the-shelf motors to their customers. Spending 3 minutes to check the condition of motors will help distributors and suppliers avoid warranty issues and increase customer satisfaction.

 

Author: Richard Scott, General Manager, ALL-TEST Pro, LLC.

 


 

Why Test Motors?

Because Motors Fail. Not all winding faults start as ground faults. Instead, they can start as a weakness in the winding insulation system that may eventually fault to ground when the motor stops running. Motor testing is integral to the...

NEW Motor Genie® App

  We are pleased to announce that the MOTOR GENIE® - Condition Calculator™ App is now available. The new MOTOR GENIE® - Condition Calculator™ App is a companion to the MOTOR GENIE® motor tester. The App allows...

The SITHE is here!!

Crane Pumps & Systems has unveiled their new chopper pump, the SITHE! Check it out in this video.   For more information call JETT Pump & Valve today at 248-673-2530 or email us at: sales@jettpump.com

NEW BLADE Grinder Pump by Barnes

Crane Pumps & Systems has released a new grinder pump! Check out the new BLADE! Call JETT Pump & Valve today at 248-673-2530 for more information or email: sales@jettpump.com

Crane Pumps & Systems Has A New Certification!

Just Announced: NSF61/ANSI 372 Certification for Weinman & Deming Horizontal Split Case pumps Crane Pumps & Systems has just announced the Weinman & Deming Horizontal Split Case pumps, Weinman End Suction pumps (375/575) and Burks...

What is Cavitation and What Causes It

  Cavitation is the formation and collapsing of cavities or bubbles in a liquid mostly developed in the areas which have relatively low pressure around the pump impeller. It occurs in the absence of the net positive suction head the pump....

Learn the Lingo: Glossary of Pump Terminology

Pumps provide an important role in our everyday lives. Where it is bringing us water or taking away waste, keeping pumps functioning is an important part of our daily society. To help you learn the lingo of the pump and repair world, below is a...

Wipes are Clogging Pipes in Macomb County

Macomb County and it's residents are feeling the costly effects that "flushable" wipes are having on maintenance to their wastewater infrastructure. This flyer has been distributed to some of the community's residents to bring...

Costly Clogging Problem Solved by Barnes SH Pumps

Back in 2011 Oak Hill Estates of Holly, MI was experiencing persistent recurring clogging- multiple times a week! The risk of overflowing the station during peak flow times could lead to heavy fines from the EPA. The lift station’s operator,...

New Energy Compliant Products

Crane Pumps & Systems announces its Department of Energy Compliant Products.  The Weinman® 375 / 575 Series End Suction Pumps, Weinman® 310 / 500 (G&K) Series End Suction Pumps, and Burks® GA & GB...

All About Check Valves

Check valves, also known as one-way or non-return valves, are unlike any other type of valve. They are one of the few self-automated valves that do not require any assistance to open or close - they are able to pass fluid in solely one direction on...

All About Check Valves

Check valves, also known as one-way or non-return valves, are unlike any other type of valve. They are one of the few self-automated valves that do not require any assistance to open or close - they are able to pass fluid in solely one direction on...
Page: 123 - All